Home / About Us / Products / Support / Contact

Products  >  Peripherals > Uninterruptible Power Supplies

Vertiv UPS GXT5-1000IRT On-Line UPS Rack/Tower 1000VA/1000W
Dove Code: UP4506 |
Manufacturer: GXT5-1000IRT2UXL

Overview

The Vertiv™ Vertiv® GXT5 UPS is an online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system.

The Vertiv® GXT5 is a single phase UPS built on the super reliable platform of GXT series- supporting over a million critical systems all over the world.

Warranty

36 Month Return to Base Warranty

Features

  • Top-level on-line double conversion UPS for mission-critical applications
  • Unity output power factor
  • LCD multi-language color display (gravity sensing)
  • On-line (VFI) mode efficiency up to 94% at full load
  • Active ECO mode efficiency up to 98%
  • Energy Star® 2.0 certified
  • Controllable and programmable output sockets
  • Integrated solution with batteries and electronics
  • External battery cabinets auto-detection
  • Operates at full power up to 40ºC (up to 50ºC with derating) Intelligent Communication ready
  • Safety Agency Approved Category B IEC 61000-4-5 Surges/Lightning protection capability)

Specifications

Rating750VA/750W
InputRated Voltage230VAC
Rated Frequency50/60Hz
Frequency Range40 to 70 Hz
Power Factor≥0.99
OutputNominal Voltage200/208/220/230/240 VAC
WaveformSine wave
Inverter Overload Capability>200% minimum 250 mS,
150 to 200% for 2 seconds;
125 to 150% for 50 seconds;
105 to 125% for 60 seconds
Efficiency in Online ModeUp to 93%
Inverter BypassUp to 98%
Output Receptacles8x EN60320/C13
Internal BatteryRated Voltage36Vdc
Charger CurrentNominal 2.2 A; Maximum 8A
TypeValve-regulated, non-spillable, lead acid
Quantity x V x Rating3 x 12V x 9.0Ah
End Cell Voltage1.67 V/cell (discharge voltage per cell will be
from 1.67 Vdc to 1.90 Vdc, can be selected by PARAMSET)
Floating VoltageEqualize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range30 Vdc to 42.3 Vdc
Internal Battery
Backup Time
(Approximate)
10% Load Capacity: 92.5 mins
20% Load Capacity: 47 mins
30% Load Capacity: 29 mins
40% Load Capacity: 20 mins
50% Load Capacity: 15 mins
60% Load Capacity: 11.5 mins
70% Load Capacity: 9.5 mins
80% Load Capacity: 8 mins
90% Load Capacity: 7 mins
100% Load Capacity: 6 mins
GeneralOperating Temperature, °CFull power up to 40 ºC
(up to 50 ºC with derating)
Storage Temperature, °C- 15 to + 40
Relative Humidity0 to 95% non-condensing
Operating ElevationUp to 3,000 m at 25°C without derating
Audible Noise<46 dBA, at 1 meter from sides,
<43 dBA, at 1 meter from rear
SafetyIEC62040-1:2008 version, GS mark;
CE: UL1778 5th Edition and
CSA 22.2 No 107.1
EMI/EMC/C-Tick EMCEN 62040-2:2006;
EN 61000-3-3:2013;
EN 61000-3-3:2013
TransportationISTA Procedure 1 A
Surge ImmunityANSI C62.41 Category B IEC 61000-4-5 Surges/Lighting
Dimensions (mm)400 (w) x 430 (d) x 85 (h)
Weight16.5kg